№ | The name of indicators | Brand | |||||
КПа-0,3 ЛЖ | КПа-0,7 ЛЖ | КПа-0,9 ЛЖ | КПа-0,3 Гн | КПа-0,7 Гн | КПа-0,9 Гн | ||
1 | type | stationary, horizontal, three-way, fire-tube | |||||
2 | Supply voltage | 50 Hz 220 or 380V * | |||||
3 | Steam capacity for normal steam, not less, kg/hour | 300 | 700 | 900 | 300 | 700 | 900 |
4 | Thermal power of the burner, MW, not less | 0,34 | 0,6 | 0,8 | 0,34 | 0,6 | 0,8 |
- natural gas consumption m3/hour, no more | - | 37 | 80 | 90 | |||
- consumption of liquid furnace fuel kg/hour, no more | 30 | 63 | 85 | - | |||
5 | Used fuel | liquid, oven | low pressure natural gas | ||||
6 | Exit to operating mode, min., no more | 25 | 25 | 25 | 30 | 30 | 30 |
7 | Steam parameters: | ||||||
-working pressure, MPa | 0,02-0,06 | ||||||
-permissible overpressure, no more, MPa | 0,07 | ||||||
-Superheated steam temperature, no more, °С | 120 | ||||||
8 | Heating surface, m2 | 16,5 | 20,2 | 22,9 | 16,5 | 20,2 | 22,9 |
9 | Overall dimensions, mm., no more | ||||||
-length (without burner) | 1780 | 2210 | 2555 | 1780 | 2210 | 2555 | |
-width (with frame and remote control) | 1925 | 1925 | 1925 | 1925 | 1925 | 1925 | |
-height (without chimney) | 2270 | 2270 | 2270 | 2270 | 2270 | 2270 | |
10 | Boiler weight, no more, kg (without mounting parts) | 1410 | 1530 | 1700 | 1410 | 1530 | 1700 |
11 | Service life, years, not less | 6 | |||||
12 | Safety valve, pcs | 2 | |||||
13 | Number of explosion valves, pcs | 1 | |||||
14 | Gas pressure control sensor, pcs | - | 1 pressure gauge | ||||
15 | Type of level gauge column | 3 electrodes | |||||
16 | Working and emergency pressure sensor | Electrical contact pressure gauge | |||||
17 | Efficiency, not less than % | 90 | 92 | ||||
18 | The noise level at the workplace does not exceed dBA | 75 | |||||
19 | Total installed power, kW, not more | 4,1 | |||||
20 | Feed water requirement: | ||||||
-suspended matter, mg/l, no more | 5 | ||||||
-transparency along the ring, cm | 50 | ||||||
-total hardness, mg eq/l, no more | 5 | ||||||
-hardness carbonate, mg. eq/l, no more | 3 | ||||||
-iron content, mg/l, no more | 0,1 | ||||||
-oxygen content, mg/l, no more | 0,03 | ||||||
-H, pH units, no more | 8 |
The boiler consists of:
Flue gases, passing through the gas path of the boiler, heat up its heat exchange surfaces. Water entering through the water treatment unit enters the boiler, where it is heated by heat exchange surfaces and evaporates. The steam passing through the superheater is superheated by the flue gases and goes to the consumer. The slags formed during the evaporation of water are periodically removed from the boiler by blowing. Boiler control and control over the technological process of steam generation is carried out using electrical equipment.
Declaration of conformity of the Eurasian Economic Union for "horizontal steam boilers"
Declaration of conformity of the Eurasian Economic Union for "horizontal steam boilers"
Certificate of conformity of the customs union for "horizontal gas heating boilers"