Three-pass horizontal fire-tube steam boilers are designed to produce steam with a temperature of no more than 120 ° C (due to the built-in superheater with an overpressure of up to 0.07 MPa (0.7 kg / cm2) for the purpose of heat supply of technological processes in the following industries: concrete goods, for steam heating, for steaming chambers, in the construction industry, in the food industry, in the production of corrugated cardboard, in the oil and gas industry, agriculture, for heat treatment of feed, pasteurization of milk, in the utilities, food and woodworking industries.
Three-pass horizontal fire-tube steam boiler - фото - 2
Three-pass horizontal fire-tube steam boilers are designed to produce steam with a temperature of no more than 120 ° C (due to the built-in superheater with an overpressure of up to 0.07 MPa (0.7 kg / cm2) for the purpose of heat supply of technological processes in the following industries: concrete goods, for steam heating, for steaming chambers, in the construction industry, in the food industry, in the production of corrugated cardboard, in the oil and gas industry, agriculture, for heat treatment of feed, pasteurization of milk, in the utilities, food and woodworking industries.
The name of indicators Brand
КПа-0,3 ЛЖ КПа-0,7 ЛЖ КПа-0,9 ЛЖ КПа-0,3 Гн КПа-0,7 Гн КПа-0,9 Гн
1 type stationary, horizontal, three-way, fire-tube
2 Supply voltage 50 Hz 220 or 380V *
3 Steam capacity for normal steam, not less, kg/hour 300 700 900 300 700 900
4 Thermal power of the burner, MW, not less 0,34 0,6 0,8 0,34 0,6 0,8
- natural gas consumption m3/hour, no more - 37 80 90
- consumption of liquid furnace fuel kg/hour, no more 30 63 85 -
5 Used fuel liquid, oven low pressure natural gas
6 Exit to operating mode, min., no more 25 25 25 30 30 30
7 Steam parameters:  
-working pressure, MPa 0,02-0,06
-permissible overpressure, no more, MPa 0,07
-Superheated steam temperature, no more, °С 120
8 Heating surface, m2 16,5 20,2 22,9 16,5 20,2 22,9
9 Overall dimensions, mm., no more  
-length (without burner) 1780 2210 2555 1780 2210 2555
-width (with frame and remote control) 1925 1925 1925 1925 1925 1925
-height (without chimney) 2270 2270 2270 2270 2270 2270
10 Boiler weight, no more, kg (without mounting parts) 1410 1530 1700 1410 1530 1700
11 Service life, years, not less 6
12 Safety valve, pcs 2
13 Number of explosion valves, pcs 1
14 Gas pressure control sensor, pcs - 1 pressure gauge 
15 Type of level gauge column 3 electrodes
16 Working and emergency pressure sensor Electrical contact pressure gauge
17 Efficiency, not less than % 90 92
18 The noise level at the workplace does not exceed dBA 75
19 Total installed power, kW, not more 4,1
20 Feed water requirement:  
-suspended matter, mg/l, no more 5
-transparency along the ring, cm 50
-total hardness, mg eq/l, no more 5
-hardness carbonate, mg. eq/l, no more 3
-iron content, mg/l, no more 0,1
-oxygen content, mg/l, no more 0,03
-H, pH units, no more 8

The boiler consists of:

  • drum;
  • front cover;
  • back covers;
  • burners;
  • water treatment unit with make-up pumps;
  • level gauge;
  • control box;
  • safety valves;
  • steam container;
  • index of levels;
  • dashboard;
  • frames with supports.

Flue gases, passing through the gas path of the boiler, heat up its heat exchange surfaces. Water entering through the water treatment unit enters the boiler, where it is heated by heat exchange surfaces and evaporates. The steam passing through the superheater is superheated by the flue gases and goes to the consumer. The slags formed during the evaporation of water are periodically removed from the boiler by blowing. Boiler control and control over the technological process of steam generation is carried out using electrical equipment.

boil_kpa_horiz_drawing

Person *
E-mail *
City
Comment *
Gallery

* - required fields

Contact us
Contact persom
Phone *
E-mail *
Your comment

JSC «Elevatormelmash» 2014

Address: Pushkin str., 79, Kropotkin,
Krasnodar territory, Russia, 352382
Opening hours: Mon-Fri 8: 00-17: 00, break 12: 00-13: 00, Sat-Sun: closed

 

The site was developed with the assistance of the export support coordination Center of the Krasnodar territory

 

Development and Marketing - WebCanape